[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-878741":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},878741,568,1,"单选题","机械通风冷却塔的进风口面积与淋水面积之比一般采用以下哪项数据？( )",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","宜为0.35～0.4",false,{"key":16,"text":17,"correct":18},"B","不宜小于0.5",true,{"key":20,"text":21,"correct":14},"C","不宜小于0.3",{"key":23,"text":24,"correct":14},"D","不宜小于0.2","在逆流塔中，空气分配装置包括进风口和导风装置；在横流塔中仅指进风口，须确定其形式、尺寸和进风方式。逆流塔的进风口指填料以下到集水池水面以上的空间。如进风口面积较大，则进口空气的流速小，不仅塔内空气分布均匀，而且气流阻力也小，但增加了塔体高度，提高了造价。反之，如进风口面积较小，则风速分布不均，进风口涡流区大，影响冷却效果。抽风逆流塔的进风口面积与淋水面积之比不小于0.5，当小于0.5时宜设导风装置以减少进口涡流。另外，《机械通风冷却塔工艺设计规范》6.3.2条：进风口的高度宜根据进风口面积与填料区面积比确定。进风口面积与填料区面积比按以下条件选取：单面进风时宜取0.35～0.45；二面进风时宜取0.4～0.5；三面进风时宜取0.45～0.55；四面进风时宜取0.5～0.6。",{"id":6,"name":27,"category":28,"favorite":29},"专业知识（给排水）","建筑工程",0]