[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-875909":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},875909,564,1,"单选题","",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","1.10～1.30kg\u002Fs，11～14kW",false,{"key":16,"text":17,"correct":18},"B","1.10～1.30kg\u002Fs，14.5～18kW",true,{"key":20,"text":21,"correct":14},"C","0.7～0.9kg\u002Fs，7～9kW",{"key":23,"text":24,"correct":14},"D","0.7～0.9kg\u002Fs，9.1～11kW","根据已知条件，送风量Q=余热\u002F送风焓差，系统冷量=余热+新风负荷=余热+新风量×室内外焓差，查h-d图，得：系统所需冷量15.5kW，室内冷负荷4.89kW，新风冷负荷7.51kW，再热量3.09kW，送风量1.19kg\u002Fs。",{"id":6,"name":27,"category":28,"favorite":29},"专业案例（暖通空调专业）","建筑工程",0]