[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-875883":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},875883,564,1,"单选题","某建筑的空调系统采用全空气系统，冬季房间的空调热负荷为100kW(冬季不加湿)，室内计算温度为20℃，冬季室外空调计算温度为-10℃，空调热源为60\u002F50℃的热水，热水量为10000kg\u002Fh，冬季的大气压力为标准大气压，空气密度为1.2kg\u002Fm3，定压比热1.0lkj\u002F(kg.℃)。试问：该系统的新风量为何值？",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","1400～1500m3\u002Fh",false,{"key":16,"text":17,"correct":18},"B","1520～1620m3\u002Fh",true,{"key":20,"text":21,"correct":14},"C","1650～1750m3\u002Fh",{"key":23,"text":24,"correct":14},"D","1770～1870m3\u002Fh","注意水的比热用4.18：10000\u002F(3600×4.18×10)-100=Q\u002F(3600×1.2×1.01×30)=1584m3\u002Fh。",{"id":6,"name":27,"category":28,"favorite":29},"专业案例（暖通空调专业）","建筑工程",0]