[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-875838":3},{"question":4,"library":24},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":21,"analysis":23},875838,564,1,"单选题","地下汽车停车库的建筑面积为4000㎡，净高度为4m，四个朝向外墙的窗井内可开启的外窗面积各为25㎡，比较合理的防排烟方案是( )。",[11,15,18,20],{"key":12,"text":13,"correct":14},"A","可以采用自然排烟",false,{"key":16,"text":17,"correct":14},"B","",{"key":19,"text":17,"correct":14},"C",{"key":21,"text":17,"correct":22},"D",true,"1)“面积超过2000㎡的地下汽车库应设置机械排烟系统”，因此，虽有可开启的外窗，仍不可以采用自然排烟。2)“每个防烟分区的建筑面积不宜超过2000㎡”，因此应设置不少于2个排烟系统。3)原则上应该按1个排烟系统负担1个防烟分区设置。但如果只设置1台排烟风机时，计算排烟量是否应该按照n个排烟系统的风量配置？《汽车库防火规范》中并没有对“担负2个或2个以上防烟分区”排烟量的规定。",{"id":6,"name":25,"category":26,"favorite":27},"专业案例（暖通空调专业）","建筑工程",0]