[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-875835":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},875835,564,1,"单选题","有AB两房间，A为外区，B为内区，室外空气温度为-12℃，室内温度为18℃，A房间外围护结构散热量为9kW， A，B房间发热量均为2kW，两房间分别送风量为3000m3\u002Fh，送风温度为30℃，求两房间的温度。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","A房间22℃，B房间32℃",true,{"key":16,"text":17,"correct":18},"B","A房间21℃，B房间30℃",false,{"key":20,"text":21,"correct":18},"C","A房间19℃，B房间32℃",{"key":23,"text":24,"correct":18},"D","A房间19℃，B房间33℃","",{"id":6,"name":27,"category":28,"favorite":29},"专业案例（暖通空调专业）","建筑工程",0]