[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-875829":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},875829,564,1,"单选题","已知：(l)某空调房间夏季室内设计温度为26℃，设计相对湿度为55%房间的热湿比为5000kj\u002Fkg。(2)空调器的表冷器的出风干球温度为14℃，相对湿度为90%，送风过程中温升为2℃。当大气压为101325Pa，房间的温度达到设计值，请绘出h-d图中的过程线，该房间的实际达到的相对湿度(查h-d图)，应为下列哪一项？",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","76%～85%",false,{"key":16,"text":17,"correct":14},"B","66%～75%",{"key":19,"text":20,"correct":21},"C","56%～65%",true,{"key":23,"text":24,"correct":14},"D","45%～55%","室内设计状态参数是26℃，相对湿度为55%，第2点相当于机组运行状态参数，不能满足设计状态，以至于要想保证室内温度为26℃，室内的相对湿度就控制不到55%状态，如右图，左边第一条线室内点26℃、55%与热湿比线相连，右边第二条线14℃、90%向上2℃，然后平移到26℃，查相对湿度。",{"id":6,"name":27,"category":28,"favorite":29},"专业案例（暖通空调专业）","建筑工程",0]