[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-875770":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},875770,564,1,"单选题","某房间冬季空调室内设计参数为：室温20℃，相对湿度35%，空调热负荷Q=lkW，室内冬季余湿为W=O.005kg\u002Fs。空调系统为直流式系统，采用湿膜加湿(按等焓加湿计算)方式，要求冬季送风温度为25℃。室外空气状态：干球温度为-6℃，相对湿度为40%。大气压力为101325Pa，计算所要求的加湿器的饱和效率。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","23%-32%",true,{"key":16,"text":17,"correct":18},"B","33%～42%",false,{"key":20,"text":21,"correct":18},"C","43%～52%",{"key":23,"text":24,"correct":18},"D","53%～62%","热湿比：ε=-lkW\u002F0.005kg\u002Fs=-200，加热后空气干球温度为31.2℃，等焓加湿后送风温度为25℃，对应饱和空气湿球温度为11.3℃。加湿器饱和效率=(加湿前空气干球温度-加湿后空气干球温度)／(加湿前空气干球温度-饱和空气湿球温度)=(31.2-25)\u002F(31.2-11.3)=31%。",{"id":6,"name":27,"category":28,"favorite":29},"专业案例（暖通空调专业）","建筑工程",0]