[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-875743":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},875743,564,1,"单选题","某空调房间冷负荷142kW，采用全空气空调，空调系统配有新风从排风中回收显热的装置(热交换率η=0.65，且新风量与排风量相等，均为送风量的15%)。已知：室外空气计算干球温度33℃，比焓90kJ\u002Fkg；室内空气计算干球温度26℃，比焓58.1kJ\u002Fkg，当采用室内空气状态下的机器露点(干球温度19℃，比焓51kJ\u002Fkg)送风时，空调设备的冷量(不计过程的冷量损失)为下列哪一项？( )",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","170～180kW",false,{"key":16,"text":17,"correct":18},"B","215～232kW",true,{"key":20,"text":21,"correct":14},"C","233～240kW",{"key":23,"text":24,"correct":14},"D","241～250kW","设送风量为G=142÷(58.1-51)=20kg\u002Fs，则空调设备冷量一室内冷负荷十新风冷负荷-回收显热=142+20×0.15×(90-58.1)-20×0.15×1.01×(33-26)×0.65=224kW。",{"id":6,"name":27,"category":28,"favorite":29},"专业案例（暖通空调专业）","建筑工程",0]