[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-875735":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},875735,564,1,"单选题","某储藏苹果的冷却物冷藏间，其计算吨位为530t，进货质量按最大设计。货物进入冷间时的温度为25℃，比焓为336.5kJ\u002Fkg；货物在冷间内终止降温时的温度为0℃，比焓为271.9kJ\u002Fkg。货物冷加工时间按24h计。货物包装材料质量系数取0.25，包装材料的比热容为1.47kJ\u002F(kg·℃)。苹果冷却初始时的呼吸热流量为0.149W\u002Fkg，终止降温时的呼吸热流量为0.019W\u002Fkg。则该冷却物冷藏间的货物热流量为( )。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","33.5～35.5kW",false,{"key":16,"text":17,"correct":14},"B","35.6～37.5kW",{"key":19,"text":20,"correct":14},"C","38.5～40.5kW",{"key":22,"text":23,"correct":24},"D","48.5～50.5kW",true,"",{"id":6,"name":27,"category":28,"favorite":29},"专业案例（暖通空调专业）","建筑工程",0]