[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-875730":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},875730,564,1,"单选题","北京地区某冷库底层的冷却间，设计温度为-2℃，一面邻外墙，外墙的热惰性指标为3.50已知：北京地区的夏季空调室外计算温度为33.2℃，夏季空调室外日平均计算温度为28.6℃；夏季空调最热月14：00的平均相对湿度为64%(对应露点温度为21.1℃)，夏季空调最热月的平均相对湿度为78%(对应露点温度为24.4℃)，试问该外墙的最小总热阻是下列哪一项？( )",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","0.20～0.23㎡·℃\u002FW",false,{"key":16,"text":17,"correct":14},"B","0.30～0.33㎡·℃\u002FW",{"key":19,"text":20,"correct":21},"C","0.36～0.39㎡·℃\u002FW",true,{"key":23,"text":24,"correct":14},"D","0.40～0.43㎡·℃\u002FW","",{"id":6,"name":27,"category":28,"favorite":29},"专业案例（暖通空调专业）","建筑工程",0]