[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-875719":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},875719,564,1,"单选题","某地冬季室外通风计算温度0℃，供暖室外计算温度-5℃，当地一散发有害气体的车间，冬季工作区供暖计算温度15℃，围护结构耗热量181.8kW。车间屋顶(高12m)设有屋顶风机进行全面通风，排风量8.8kg\u002Fs。当采用全新风集中热风供暖系统，送风量为8kg\u002Fs，车间屋顶梯度为0.5℃\u002Fm时，热风系统的送风温度为下列哪一项？( )",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","44.1～44.6℃",false,{"key":16,"text":17,"correct":18},"B","44.8～45.2℃",true,{"key":20,"text":21,"correct":14},"C","45.8～46.2℃",{"key":23,"text":24,"correct":14},"D","46.8～47.2℃","",{"id":6,"name":27,"category":28,"favorite":29},"专业案例（暖通空调专业）","建筑工程",0]