[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-875705":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},875705,564,1,"单选题","某30万㎡的小区，节能改造，室外供热水管道保温，用玻璃棉管壳[保温层平均使用温度k=60℃时，导热系数为0.034W／(m·K)]代替原来用的150mm厚的水泥膨胀珍珠岩[导热系数为0.16W／(m·K)]，且供回水温由95／70℃变为130\u002F70℃，地沟内温度为40℃，那么改造后的D325×8管道的保温材料厚度应为下列哪一项？",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","30mm",false,{"key":16,"text":17,"correct":14},"B","40mm",{"key":19,"text":20,"correct":21},"C","50mm",true,{"key":23,"text":24,"correct":14},"D","60mm","",{"id":6,"name":27,"category":28,"favorite":29},"专业案例（暖通空调专业）","建筑工程",0]