[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-875668":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},875668,564,1,"单选题","某车间设有局部排风系统，局部排风量为0.56kg\u002Fs，冬季室内工作区温度为15℃，冬季通风室外计算温度为-15℃，采暖室外计算温度为-25℃(大气压为标准大气压)，空气定压比热1.01kJ(kg.℃)。围护结构耗热量为8.8kW，室内维持负压，机械进风量为排风量的90%，试求机械通风量和送风温度为下列何项？",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","0.3～0.53kg\u002Fs，29～32℃",false,{"key":16,"text":17,"correct":14},"B","0.54～0.65kg\u002Fs，29～32℃",{"key":19,"text":20,"correct":14},"C","0.54～0.65kg\u002Fs，33～36.5℃",{"key":22,"text":23,"correct":24},"D","0.3～0.53kg\u002Fs，36.6～38.5℃",true,"",{"id":6,"name":27,"category":28,"favorite":29},"专业案例（暖通空调专业）","建筑工程",0]