[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-875651":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},875651,564,1,"单选题","某办公楼采用冷辐射吊顶+新风空调系统，室温为26℃的会议室湿负荷为3kg\u002Fh，新风量为900kg\u002Fh，辐射板供水温度20℃，大气压101.3kPa。为了防止结露，新风露点温度应低于( )。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","19℃",false,{"key":16,"text":17,"correct":18},"B","16℃",true,{"key":20,"text":21,"correct":14},"C","13℃",{"key":23,"text":24,"correct":14},"D","12℃","",{"id":6,"name":27,"category":28,"favorite":29},"专业案例（暖通空调专业）","建筑工程",0]