[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-875628":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},875628,564,1,"单选题","某商住楼，首层和2层是三班制工场，供暖室内计算温度16℃，3层及以上是住宅，每层6户，每户145㎡，供暖室内计算温度为18℃，每户住宅计算供暖热负荷约为4kW，2，3层间楼板传热系数为2W\u002F(㎡·K)，房间楼板传热的处理方法按有关设计规范下列哪一项是正确的？( )",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","计算3层向2层传热量，但3层房间供暖热负荷不增加",false,{"key":16,"text":17,"correct":18},"B","计算3层向2层传热量，计入3层供暖热负荷中",true,{"key":20,"text":21,"correct":14},"C","不需要计算2，3层之间的楼板的传热量",{"key":23,"text":24,"correct":14},"D","计算3层向2层传热量，但2层房间的供暖负荷可不减少","",{"id":6,"name":27,"category":28,"favorite":29},"专业案例（暖通空调专业）","建筑工程",0]