[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-875625":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},875625,564,1,"单选题","某建筑的设计采暖负荷为200kW，供回水温度为80℃\u002F60℃，计算阻力损失为50kP A，其入口处外网的实际供回水压差为40kP A，则该建筑采暖系统的实际热水循环量应为( )kg\u002Fh。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","6550～6950",false,{"key":16,"text":17,"correct":14},"B","7000～7450",{"key":19,"text":20,"correct":21},"C","7500～8000",true,{"key":23,"text":24,"correct":14},"D","8050～8550","",{"id":6,"name":27,"category":28,"favorite":29},"专业案例（暖通空调专业）","建筑工程",0]