[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-875617":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},875617,564,1,"单选题","某大楼安装一台额定冷量为500kW的冷水机组(COP=5)，系统冷冻水水泵功率为25kW，冷却水泵功率为20kW，冷却塔风机功率为4kW，设水系统按定水量方式运行，且水泵和风机均处于额定工况运行，冷机的COP在部分负荷时维持不变。已知大楼整个供冷季100%、75%、50%、25%负荷的时间份额依次为0.1、0.2、0.4和0.3，则该空调系统在整个供冷季的系统能效比(不考虑末端能耗)为( )。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","4.5～5.0",false,{"key":16,"text":17,"correct":14},"B","3.2～3.5",{"key":19,"text":20,"correct":21},"C","2.4～2.7",true,{"key":23,"text":24,"correct":14},"D","1.6～1.9","",{"id":6,"name":27,"category":28,"favorite":29},"专业案例（暖通空调专业）","建筑工程",0]