[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-875612":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},875612,564,1,"单选题","某工程确定选用名义制冷量为200kW的螺杆式冷水机组，由生产厂家的样本查得：该机组在冷却水进口温度30℃，出口温度35℃时，冷凝温度为38℃；采用卧式壳管式冷凝器，传热系数为750W\u002F(㎡·K)，冷凝器排热量为232.8kW，水侧污垢热阻为0.086㎡·K\u002FkW。已知使用地点水质较差，污垢热阻为0.3㎡·K\u002FkW。使用当地水质时，壳管式冷凝器的传热系数是( )。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","712.0～713.0W\u002F(㎡·K)",false,{"key":16,"text":17,"correct":18},"B","646.0～647.0W\u002F(㎡·K)",true,{"key":20,"text":21,"correct":14},"C","574.0～575.0W\u002F(㎡·K)",{"key":23,"text":24,"correct":14},"D","448.0～449.0W\u002F(㎡·K)","",{"id":6,"name":27,"category":28,"favorite":29},"专业案例（暖通空调专业）","建筑工程",0]