[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-875601":3},{"question":4,"library":22},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":20,"analysis":13},875601,564,1,"单选题","某水冷离心式冷水机组，设计工况下的制冷量为500kW，COP为5.0，冷却水进出水温差为5℃。采用横流型冷却塔，冷却塔设在裙房屋面，其集水盘水面与机房内冷却水泵的高差为18m。冷却塔喷淋口距离冷却水集水盘水面的高差为5m，喷淋口出水压力为2m，冷却水管路总阻力为5m，冷凝器水阻力为8m。忽略冷却水泵及冷凝水管与环境换热对冷凝负荷的影响。冷却水泵的扬程和流量(不考虑安全系数)为( )。",[11,15,17,19],{"key":12,"text":13,"correct":14},"A","",false,{"key":16,"text":13,"correct":14},"B",{"key":18,"text":13,"correct":14},"C",{"key":20,"text":13,"correct":21},"D",true,{"id":6,"name":23,"category":24,"favorite":25},"专业案例（暖通空调专业）","建筑工程",0]