[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-875599":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},875599,564,1,"单选题","某乙类厂房，冬季工作区供暖计算温度15℃，厂房围护结构耗热量Q=313.1kW，厂房全面排风量L=42000m3\u002Fh；厂房采用集中热风采暖系统，设计送风量G=12kg\u002Fs，则该系统冬季的设计送风温度tjj应为下列何项？(注：当地标准大气压力，室内外空气密度取均为1.2kg\u002Fm3，空气比热容cp=1.011kj\u002F(kg·℃)，冬季通风室外计算温度-10℃)",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","40～41.9℃",false,{"key":16,"text":17,"correct":14},"B","42～43.9℃",{"key":19,"text":20,"correct":21},"C","44～45.9℃",true,{"key":23,"text":24,"correct":14},"D","46～48.9℃","",{"id":6,"name":27,"category":28,"favorite":29},"专业案例（暖通空调专业）","建筑工程",0]