[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-875597":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},875597,564,1,"单选题","某冷水系统有2台同型号的冷水机组，已知机组在100%负荷时的COP为5.7，50%负荷时的COP为6.7，当系统的负荷正好等于1台机组的额定负荷时，2台机组同时运行相对于1台机组运行的供冷节能率为( )。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","5%",false,{"key":16,"text":17,"correct":14},"B","10%",{"key":19,"text":20,"correct":21},"C","15%",true,{"key":23,"text":24,"correct":14},"D","18%","",{"id":6,"name":27,"category":28,"favorite":29},"专业案例（暖通空调专业）","建筑工程",0]