[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-875577":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},875577,564,1,"单选题","某建筑物拟采用冰蓄冷空调系统，选择部分蓄冰方式。已知：电价谷段时间为23：00-7：00；制冷机白天空调时段运行8h；采用三级离心制冷机，其制冰时的制冷能力变化率为0.75；设计日空调最大小时冷负荷为22293kW，设计日空调运行15h，平均负荷系数取0.80按平均法估算的该空调系统设计日总冷负荷、按部分蓄冰方式蓄冷时制冷机标定制冷量、蓄冷装置有效容量分别为( )kW·h。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","267516，19108，114618",true,{"key":16,"text":17,"correct":18},"B","334395，23885，143310",false,{"key":20,"text":21,"correct":18},"C","267516，16720，100320",{"key":23,"text":24,"correct":18},"D","267516，19108，152846","",{"id":6,"name":27,"category":28,"favorite":29},"专业案例（暖通空调专业）","建筑工程",0]