[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-875569":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},875569,564,1,"单选题","已知一台通风兼排烟双速离心风机，低速时风机铭牌风量为12450m3／h，风压为431Pa。已知当地的大气压力为B=101.3kPa，现要求高温时排风量为17430m3／h，排气温度为270℃，若风机、电机及传动效率在内的风机总效率为0.52，求该配套风机的电机功率至少应为多少？",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","4kW",false,{"key":16,"text":17,"correct":18},"B","5.5kW",true,{"key":20,"text":21,"correct":14},"C","11kW",{"key":23,"text":24,"correct":14},"D","15kW","",{"id":6,"name":27,"category":28,"favorite":29},"专业案例（暖通空调专业）","建筑工程",0]