[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-875548":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},875548,564,1,"单选题","一栋楼的空调水系统参数如下：冷水机组的阻力为100kPa，过滤器、分集水器等管道附件的阻力为80kPa，管道为异程系统，最远环路的阻力最大，其单程长度100m，比摩阻均按120Pa\u002Fm估算，管道局部阻力为沿程阻力的50%，最远环路空调末端阻力为50kPa(包括阀门)，则循环水泵的扬程应为( )。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","20～25m",false,{"key":16,"text":17,"correct":14},"B","25～27m",{"key":19,"text":20,"correct":14},"C","27～29m",{"key":22,"text":23,"correct":24},"D","29～31m",true,"水泵扬程的安全系数取1.1。环路的总管长为两倍单程管长，因此循环水泵的扬程为：H=(100×2×0.12×1.5+100+80+50)×1.1≈293kPa，即29.3m。",{"id":6,"name":27,"category":28,"favorite":29},"专业案例（暖通空调专业）","建筑工程",0]