[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-875541":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},875541,564,1,"单选题","某办公楼采用变风量空调系统，空调冷水系统为一级泵变流量系统，空调机组冷水管路上设置电动调节阀，采用1台变频水泵控制供回水总管的压差恒定。假设水泵的流量与频率呈正比关系，当水泵运行频率为40Hz时，水泵效率下降了10%，这时该水泵的能耗比工频时减少( )。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","11%",true,{"key":16,"text":17,"correct":18},"B","18%",false,{"key":20,"text":21,"correct":18},"C","32%",{"key":23,"text":24,"correct":18},"D","43%","",{"id":6,"name":27,"category":28,"favorite":29},"专业案例（暖通空调专业）","建筑工程",0]