[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-875539":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},875539,564,1,"单选题","某变制冷剂流量(VRV)系统，标准工况及配管情况下系统性能系数COP一2.7，而此系统最远末端超出额定配管长度为120m，吸气管平均阻力相当于0.06℃／m，液管平均阻力相当于0.03℃\u002Fm，问该系统满负荷时，系统的实际性能系数应为下列何值？注：蒸发温度增／降1℃，COP约增／降3%；冷凝温度增／降1℃，COP约降／增1.5%。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","＜1.9",true,{"key":16,"text":17,"correct":18},"B","1.9～2.O",false,{"key":20,"text":21,"correct":18},"C","2.1～2.2",{"key":23,"text":24,"correct":18},"D","＞2.2","",{"id":6,"name":27,"category":28,"favorite":29},"专业案例（暖通空调专业）","建筑工程",0]