[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-875536":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},875536,564,1,"单选题","某北向房间外墙和外窗的基本耗热量为3500W，朝向修正率和风力附加率各为10%，冷风渗透耗热量为2000W，房间高度为5.5m，通过房间的热管道的有效稳定散热量为2000W，其供暖热负荷为( )。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","4326W",true,{"key":16,"text":17,"correct":18},"B","4366W",false,{"key":20,"text":21,"correct":18},"C","6326W",{"key":23,"text":24,"correct":18},"D","6366W","1)围护结构的基本耗热量为3500W。2)围护结构的附加耗热量为3500×0.2=700W。3)高度附加耗热量为(3500+700)×0.03=126W。4)房间供暖热负荷为3500+700+126+2000-2000=4326W。",{"id":6,"name":27,"category":28,"favorite":29},"专业案例（暖通空调专业）","建筑工程",0]