[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-875520":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},875520,564,1,"单选题","某建筑空调采用地埋管地源热泵，设计参数为制冷量2000kW。全年空调制冷当量满负荷运行时间为1000h，制热量为2500kW，全年空调供热当量满负荷运行时间为800h，设热泵机组的制冷、制热的能效比全年均为5.0，辅助冷却塔的冷却能力不随负荷变化，不计水泵等的附加散热量。要维持土壤全年自身热平衡(不考虑土壤与外界的换热)，下列哪一项措施是正确的？( )",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","设置全年冷却能力为800000kW·h的辅助冷却塔",true,{"key":16,"text":17,"correct":18},"B","设置全年冷却能力为400000kW·h的辅助冷却塔",false,{"key":20,"text":21,"correct":18},"C","设置全年加热能力为400000kW·h的辅助供热设备",{"key":23,"text":24,"correct":18},"D","系统已能实现土壤全年热平衡，不需设置任何辅助设备","",{"id":6,"name":27,"category":28,"favorite":29},"专业案例（暖通空调专业）","建筑工程",0]