[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-875508":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},875508,564,1,"单选题","某房间吊顶中有一段镀锌钢板的空调送风管，其设计空气温度为10℃，设计采用了20mm橡塑海绵保温层，并要求保温材料的导热系数不大于0.03W\u002F(m·K)，运行过程中发现该风管保温层外表面出现了冷凝水，实测风管的环境温度为30℃，相对湿度为75%，与设计工况相同，管内空气温度为8℃，检查发现保温层厚度满足要求，风管内、外表面的表面传热系数分别按25W\u002F(㎡·K)和8W\u002F(㎡·K)计算，计算中风管热阻可以忽略。根据测试结果分析，对结露原因的判断中正确的是( )。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","结露是由于设计的保温层厚度太小造成的",false,{"key":16,"text":17,"correct":14},"B","结露是由于运行参数不对、送风温度太低造成的",{"key":19,"text":20,"correct":21},"C","结露是由于材料质量问题造成的",true,{"key":23,"text":24,"correct":14},"D","结露是由于综合因素造成的，因此无法准确判断责任方","",{"id":6,"name":27,"category":28,"favorite":29},"专业案例（暖通空调专业）","建筑工程",0]