[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-875490":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},875490,564,1,"单选题","某商住楼，每层建筑面积960㎡，首层和2层是商场，供暖室内计算温度18℃，3层及以上是住宅，每层8户，供暖室内计算温度20℃，每户住宅计算供暖负荷约为5kW。2，3层之间的楼板传热系数为2.0W\u002F(㎡·K)。对“相邻房间传热”的处理，下列哪一种是正确的？( )",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","不需要计算2，3层之间的传热量",true,{"key":16,"text":17,"correct":18},"B","计算3层向2层的传热量，作为3层房间的供暖负荷",false,{"key":20,"text":21,"correct":18},"C","计算3层向2层的传热量，增加3层房间的供暖负荷和减少2层房间的供暖负荷",{"key":23,"text":24,"correct":18},"D","2，3层之间的楼板增加保温层，降低楼板的传热系数","本实例温度差小于5℃。相邻房间楼板传热量为960×2×2=3840W，每户平均488W，占每户住宅计算供暖负荷(约为5kW)的9.6%，小于10%，因此不需要计算2，3层之间的传热量。",{"id":6,"name":27,"category":28,"favorite":29},"专业案例（暖通空调专业）","建筑工程",0]