[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-875488":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},875488,564,1,"单选题","某市一装配式冷库用于贮藏冻肉。装配式冷库的库板为1mm厚压花铝板夹150mm厚聚氨酯隔热层。导热系数，铝板为202.940W\u002F(m·℃)，聚氨酯隔热材料为0.031W\u002F(m·℃)。蓄热系数，铝板为182.59W\u002F(㎡·℃)，聚氨酯隔热材料为0.28W\u002F(㎡·℃)。冷藏间设计温度-18℃。该市夏季通风室外计算干球温度为33℃；夏季空调室外计算干球温度为36.5℃；夏季空调日平均温度为32.5℃。围护结构高温侧空气露点温度为27.41℃。围护结构外表面热阻为0.043㎡·℃\u002FW。热阻修正系数为b，当围护结构热惰性指标D≤4时，b=1.2；其他围护结构，b=1.0。则该装配式冷库围护结构的最小总热阻是( )。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","0.30～0.35㎡·℃\u002FW",false,{"key":16,"text":17,"correct":14},"B","0.46～0.50㎡·℃\u002FW",{"key":19,"text":20,"correct":21},"C","0.51～0.55㎡·℃\u002FW",true,{"key":23,"text":24,"correct":14},"D","0.40～0.45㎡·℃\u002FW","",{"id":6,"name":27,"category":28,"favorite":29},"专业案例（暖通空调专业）","建筑工程",0]