[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-875481":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},875481,564,1,"单选题","南方某办公建筑拟设蓄冰空调，该大楼设计日的总负荷为12045kW·h，当地电费的谷价时段为23：00-07：00，采用双工况螺杆式制冷机夜间低谷电价时段制冰蓄冷(制冰时制冷能力的变化率为0.7)，白天机组在空调工况运行9h，制冷站设计日附加系数为1.0，试问：在部分负荷蓄冷的条件下，该项目蓄冷装置最低有效容量Q。应为( )。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","4450～4650kW",true,{"key":16,"text":17,"correct":18},"B","4700～4850kW",false,{"key":20,"text":21,"correct":18},"C","4950～5150kW",{"key":23,"text":24,"correct":18},"D","5250～5450kW","",{"id":6,"name":27,"category":28,"favorite":29},"专业案例（暖通空调专业）","建筑工程",0]