[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-875477":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},875477,564,1,"单选题","某机械循环热水供暖系统包括南北两个并联循环环路1和2，系统设计供／回水温度为95\u002F70℃，总热负荷为74800W，水力计算环路1的压力损失为4513Pa，流量为1196kg\u002Fh，环路2的压力损失为4100Pa，流量为1180kg\u002Fh，如果采用不等温降方法进行水力计算，环路1最远立管温降30℃，则实际温降为多少？( )。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","28.4℃",true,{"key":16,"text":17,"correct":18},"B","30℃",false,{"key":20,"text":21,"correct":18},"C","25℃",{"key":23,"text":24,"correct":18},"D","31.7℃","",{"id":6,"name":27,"category":28,"favorite":29},"专业案例（暖通空调专业）","建筑工程",0]