[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-875319":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},875319,563,1,"单选题","某高层建筑室内消火栓给水系统采用临时高压系统，消防水泵出水口与最不利点处消火栓栓口的几何高差为50m，灭火时消防水泵出水口处压力表读数为1.0MPa。若水泵出水口处速度水头为2m水柱，最不利点处消火栓栓口的速度水头为3m水柱，水枪充实水柱不小于13m，水泵出水口处至最不利消火栓栓口管路的水头损失为0.1MPa。则该消火栓给水系统最不利点处消火栓栓口的动压应为下列哪项？注：1.0MPa=100m水柱( )",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","0.39MPa",true,{"key":16,"text":17,"correct":18},"B","0.37MPa",false,{"key":20,"text":21,"correct":18},"C","0.35MPa",{"key":23,"text":24,"correct":18},"D","0.03MPa","最不利点处消火栓栓口的动压=水泵出水口处压力+水泵出水口，处速度水头-水泵出水口处至最不利消火栓栓口的几何高差-水泵出水口处至最不利消火栓栓口管路的水头损失-消水栓栓口的速度水头=100+2-50-10-3=39m水柱=0.39MPa",{"id":6,"name":27,"category":28,"favorite":29},"专业案例（给排水）","建筑工程",0]