[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-875283":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},875283,563,1,"单选题","",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","6.17L\u002Fs",false,{"key":16,"text":17,"correct":14},"B","6.45L\u002Fs",{"key":19,"text":20,"correct":14},"C","4.58L\u002Fs",{"key":22,"text":23,"correct":24},"D","5.24L\u002Fs",true,"查《自动喷水灭火系统设计规范》附录A，图书馆书库为中危Ⅱ级，其喷水强度为8L\u002F(min·㎡)，每个喷头的保护面积为3.4m×3.4m那么4只喷头在不考虑损失的前提下，流量之和为：8×3.4×3.4×4\u002F60=6.17L\u002Fs从图示及题意知，喷头1～4为最不利点处喷头，按照规范9.1.4条，其喷水强度校核值最低为规范规定值的8L\u002F(min·㎡)的0.85倍，则最小流量为6.17×0.85=5.24L\u002Fs。",{"id":6,"name":27,"category":28,"favorite":29},"专业案例（给排水）","建筑工程",0]