[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-875269":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},875269,563,1,"单选题","某公共建筑集中热水供应系统设计小时耗热量为480kW，采用表压0.2MPa饱和蒸汽为热媒的半容积式加热器，冷水温度50℃，设计热水温度65℃，热媒冷凝回水100℃，热水密度均以1kg\u002FL计，则水加热器的最小贮热水量容积应为何值？( )",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","6397L",false,{"key":16,"text":17,"correct":14},"B","1892L",{"key":19,"text":20,"correct":21},"C","1720L",true,{"key":23,"text":24,"correct":14},"D","103L","",{"id":6,"name":27,"category":28,"favorite":29},"专业案例（给排水）","建筑工程",0]