[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-875259":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},875259,563,1,"单选题","",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","2处",false,{"key":16,"text":17,"correct":14},"B","3处",{"key":19,"text":20,"correct":14},"C","4处",{"key":22,"text":23,"correct":24},"D","5处",true,"《建筑给水排水设计规范》第3.4.7.1条：直接从城镇给水管网接入小区或建筑物的引入管设止回阀。《建筑给水排水设计规范》第3.4.5.4条：各分立管设置阀门。《建筑给水排水设计规范》第3.4.5.4条：人户管和水表前，设阀门。《建筑给水排水设计规范》第3.2.5A.1条：单独接出消防用水管道时，在消防用水管道的起段应设倒流防止器。《建筑给水排水设计规范》第3.4.5.4条：各分立管设置阀门。分别对应下面(1)～(5)项：(1)引入管漏设止回阀；(2)生活立管漏设阀门；(3)分户水表前漏设阀门；(4)消防支管上漏设倒流防止器；(5)消防立管漏设阀门。",{"id":6,"name":27,"category":28,"favorite":29},"专业案例（给排水）","建筑工程",0]