[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-875254":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},875254,563,1,"单选题","某12层住宅楼采用恒压变频调速泵装置供水。住宅层高均为3m。首层住宅楼面标高为±0.00。水泵设在该楼地下2层，水泵出水恒压设定为0.64MPa(该处标高为-6.00m)，该处至最高层住户管处的总水头损失为0.14MPa；最高层住户入户管处的设计水压0.1MPa，各层入户管均高于所在楼面1m，则该住宅楼哪几层人户管处的供水压力超过规范规定？( )",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","2层及以下",false,{"key":16,"text":17,"correct":14},"B","4层及以下",{"key":19,"text":20,"correct":21},"C","6层及以下",true,{"key":23,"text":24,"correct":14},"D","8层及以下","(1)根据《建筑给水排水设计规范》第3.3.5A条：居住建筑人户管的给水压力不应大于0.35MPa。设需减压的层数为N，入户管均高于所在楼面1m，则该层出水管的标高为3N-2；最高层的出水管的标高为3N-2=12×3-2=34m；同时考虑地下的6m，则总的管道长为40m。(2)层数为N，则从下往上计算时：0.64-0.06-[(3N-2)\u002F10-(3N-2)×0.14]\u002F40≥0.35，则N≤6.35，故取6层及以下人户管处的供水压力超过规范规定。",{"id":6,"name":27,"category":28,"favorite":29},"专业案例（给排水）","建筑工程",0]