[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-875205":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},875205,563,1,"单选题","某座厂房，室内消火栓系统采用水塔供水的常高压系统，设有消火栓的最高层地面标高为15.0m(相对于室内±0.00)，水塔出水管至最不利消火栓的沿程水头损失为10m，水塔内最低有效水位距内底600mm。水塔内底相对于±0.00的标高(m)不应小于下列哪项？写出计算过程。( )",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","53.7",false,{"key":16,"text":17,"correct":14},"B","62.6",{"key":19,"text":20,"correct":21},"C","63.7",true,{"key":23,"text":24,"correct":14},"D","64.3","计算可得：15+1.1+35+10×(1+10%)×(1+20%)-0.60=63.7m",{"id":6,"name":27,"category":28,"favorite":29},"专业案例（给排水）","建筑工程",0]