[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-875142":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},875142,563,1,"单选题","某城镇为单一水厂供水系统，水厂清水池最高水位标高112.00m，最低水位标高109.00m。拟在标高158.00m处设一水柜有效水深为4.0m的网前水塔，要求保证最不利控制点处(控制点地面标高149.00m)的建筑三层正常用水，并确保管网满足低压制消防要求。按最高供水时供水量及消防时流量计算的从水塔到最不控制点处的管网总水头损失为15.00m及19.00m，计算网前水塔水柜底离地面的设置高度(m)为下列哪项？( )",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","12",false,{"key":16,"text":17,"correct":14},"B","20",{"key":19,"text":20,"correct":14},"C","18",{"key":22,"text":23,"correct":24},"D","22",true,"控制点正常时的水压标高需：149+16=165m。控制点消防时的水压标高需：149+10=159m。按正常工况算水塔高度：165+15-158=22m。按消防工况算水塔高度：159+19-158=20m。因此水塔高度应为22m。",{"id":6,"name":27,"category":28,"favorite":29},"专业案例（给排水）","建筑工程",0]