[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-875011":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},875011,562,1,"单选题","某供暖系统供回水温度为95℃\u002F70℃，最高建筑物为七层，高度为25m。散热器选用铸铁160翼型，承受压力为400kPa(相当于40mH2O)，设锅炉房的地坪标高为+0.00m，最高建筑物地坪标高为4.5m，管网最低建筑地坪标高为3.81m，则静水压线位置为( )kPa。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","470",false,{"key":16,"text":17,"correct":14},"B","520",{"key":19,"text":20,"correct":14},"C","280",{"key":22,"text":23,"correct":24},"D","330",true,"保证最高点用户系统不倒空所需的压力不低于：(4.5+25+3)mH2O=32.5mH2O=325kPa保证最低点用户系统散热器不压裂，所需的压力不高于最大允许压力：(3.81+40)mH2O=43.81mH2O=438.1kPa式中3m为安全值。结论：静水压线在325～438.1kPa之间均合适，因此取静水压线为330kPa能满足要求。",{"id":6,"name":27,"category":28,"favorite":29},"专业案例（动力专业）","建筑工程",0]