[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-874823":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},874823,562,1,"单选题","北方某房间有一面西外墙和西外窗，经计算西外墙的基本耗热量为1000W，西外窗的基本耗热量为450W，房间高度为6.5m，通过外窗的冷风渗透耗热量为200W。则该房间的总热负荷为( )。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","1595W",false,{"key":16,"text":17,"correct":14},"B","1760W",{"key":19,"text":20,"correct":14},"C","1764W",{"key":22,"text":23,"correct":24},"D","1799W",true,"该房间的总热负荷为：Q=(1000+450)×(1+0.05)×(1+0.05)+200=1799W",{"id":6,"name":27,"category":28,"favorite":29},"专业案例（动力专业）","建筑工程",0]