[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-867490":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},867490,558,1,"单选题","《施工现场临时用电安全技术规范》规定，电缆直接埋地敷设的深度不应小于0.7m，并应在电缆紧邻上、下、左、右侧均匀敷设不小于（ ）厚的细砂，然后覆盖砖或混凝土板等硬质保护层。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","30MM",false,{"key":16,"text":17,"correct":14},"B","35MM",{"key":19,"text":20,"correct":21},"C","50MM",true,{"key":23,"text":24,"correct":14},"D","60MM","电缆敷设应采用埋地或架空两种方式，严禁沿地面明设，以防机械损伤和介质腐蚀。直埋电缆在穿越建筑物、构筑物、道路、易受机械损伤和介质腐蚀场所及引出地面从2m高到地下0.2m处必须加设防护套管，防护套管内径不应小于电缆外径的1.5倍。电缆埋地敷设宜选用恺装电缆，电缆直接埋地敷设的深度不应小于0.7m，并应在电缆紧邻上、下、左、右侧均匀敷设不小于50mm厚的细沙，然后覆盖砖或混凝土板等硬质保护层。电缆接线盒应能防水、防尘、防机械损伤，并远离易燃、易爆、易腐蚀场所。",{"id":6,"name":27,"category":28,"favorite":29},"江苏省C2证（土建安全员）","建筑工程",0]