[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-861288":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},861288,553,2,"多选题","在建工程作业场所的临时疏散通道应与在建工程结构施工同步设置（）。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","应采用不燃、难燃材料建造",true,{"key":16,"text":17,"correct":14},"B","耐火极限不应低于0.5小时",{"key":19,"text":20,"correct":21},"C","耐火极限不应低于3.0H",false,{"key":23,"text":24,"correct":14},"D","临时疏散通道应设置明显的疏散指示标志",{"key":26,"text":27,"correct":14},"E","临时疏散通道应设置照明设施","ABDE","在建工程防火（1）在建工程作业场所的临时疏散通道应采用不燃或难燃材料建造，并与在建工程结构施工同步设置，也可利用在建工程施工完毕的水平结构、楼梯。（2）在建工程内临时疏散通道的设置应符合下列规定：1）疏散通道的耐火极限不应低于0.5h。2）设置在地面上的临时疏散通道，其净宽度不应小于1.5m；利用在建工程施工完毕的水平结构、楼梯作临时疏散通道时，其净宽度不宜小于1.0m；用于疏散的爬梯及设置在脚手架上的临时疏散通道，其净宽度不应小于0.6m。3）临时疏散通道为坡道，且坡度大于25°时，应修建楼梯或台阶踏步或设置防滑条。4）临时疏散通道不宜采用爬梯。确需采用时，应采取可靠固定措施。5）疏散通道的侧面若为临空面，应沿临空面设置高度不小于1.2m的防护栏杆。6）当临时疏散通道搭设在脚手架上时，脚手架应采用不燃材料搭设。7）临时疏散通道应设置明显的疏散指示标识。8）临时疏散通道应设置照明设施。",{"id":6,"name":31,"category":32,"favorite":33},"B证（项目负责人）","建筑工程",0]