[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-850025":3},{"question":4,"library":23},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":22},850025,466,1,"单选题","我们可以使用化学试纸对氨制冷系统进行检漏,如果发生氨泄漏,则试纸的颜色变成()。",[11,15,19],{"key":12,"text":13,"correct":14},"A","浅蓝色",false,{"key":16,"text":17,"correct":18},"B","粉红色",true,{"key":20,"text":21,"correct":14},"C","深绿色","常用的制冷系统的检漏方法有两种，即肥皂水检漏和充氨检漏。(1)肥皂水检漏 肥皂水检漏为被检，其方法是:对整个系统内充压，当压力，上升到规定值后，用肥皂水布于管道各接头、焊点、法兰等处，如有气泡冒出，说明该处渗漏，应作为记号，进行修补。此法简单易行，效果良好。(2)充氨检漏 首先对系统进行抽真空处理，然后分段、分库方进行充氨检漏。充氨量不能太多，一般充入量为0.196MPa为宜。充氨后用酚酞试纸沾水检测各焊口、接头及法兰等处，正常时试纸的颜色不变化，若试纸变成红色，说明该处泄漏。充氨检测时应注意两点:一是在使用酚酞试纸前应将管道上的肥皂水擦净，因为肥皂含碱性物质，引起化学反应而造成误判;二是在确定漏点后，应将系统中的氨吸净，并用压缩气体吹洗一遍才能进行焊接，以防止带氨焊接引起爆炸。",{"id":6,"name":24,"category":25,"favorite":26},"制冷与空调设备运行操作","特种作业",0]