[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-850021":3},{"question":4,"library":23},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":22},850021,466,1,"单选题","溴化锂吸收式制冷机组的冷媒水温度越来越高,其可能的原因是()。",[11,15,19],{"key":12,"text":13,"correct":14},"A","冷媒水不足",false,{"key":16,"text":17,"correct":18},"B","冷媒水太多",true,{"key":20,"text":21,"correct":14},"C","外界负荷小于制冷能力","溴化锂吸收式制冷机因发生器容汽空间的垂直高度太小，冷剂蒸汽的流速太高或挡液板结构不良，或者由于加热蒸汽压力突然升高，稀溶液浓度较低，溶液的pH值太大，冷却水温度太低等原因而造成发生器中溶液强烈沸腾，使发生器中的溴化锂液滴被冷剂蒸汽带入冷凝器;吸收器溴化锂液滴也有可能溅入蒸发器，造成冷剂水污染。可以从蒸发器液囊视镜观察冷剂水的颜色，发现冷剂水带黄色时，有污染之疑。这时可通过冷剂水取样阀取样，测定冷剂水的密度，若测得的密度不大于1.04kg\u002Fl时，一般不作处理;当大于1.04kg\u002Fl时，可通过冷剂水旁通阀使冷剂水再生，直至冷剂水的密度达到合格。",{"id":6,"name":24,"category":25,"favorite":26},"制冷与空调设备运行操作","特种作业",0]