[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-849916":3},{"question":4,"library":23},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":22},849916,466,1,"单选题","在溴化锂吸收式制冷机组中,为了防止冷剂水冻结导致蒸发器管子破裂,通常要在冷剂水或冷媒水管道上安装温度控制器,一般冷剂水报警温度的设定给定值为()。",[11,15,18],{"key":12,"text":13,"correct":14},"A","3℃-4℃",false,{"key":16,"text":17,"correct":14},"B","1℃-2℃",{"key":19,"text":20,"correct":21},"C","2℃-3℃",true,"在冷剂水或冷媒水管道上安装温度控制器。这种温度控制器是一-种具有单边差动的双位控制器。该控制器参数设定值包括设定给定值和设定差动值。当冷剂水或冷媒水温度低于设定给定值时，温度遥控器动作,启动报警信号，同时工作热源被切断，机组转入稀释运行状态。当冷媒水水温回升至高于设定给定值与设定差动值的和后，机组重新投入正常运行状态。当冷媒水水温回升至高于设定给定值与设定差动值的和后，机组重新投入正常运行。一般冷剂水报警温度的设定给定值为2°C~3°C,设定差动值为1°C~2°C;冷媒水报警温度设定给定值为3°C~4°C,设定差动值为1°C~2°C。所用温度控制器包括WTZK-50-C型温度控制器，新机型机组广泛采用温度传感器与PLC控制。",{"id":6,"name":24,"category":25,"favorite":26},"制冷与空调设备运行操作","特种作业",0]