[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-849866":3},{"question":4,"library":23},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":22},849866,466,1,"单选题","在溴化锂吸收式制冷机组中,会造成冷剂水污染的原因不包括()。",[11,15,19],{"key":12,"text":13,"correct":14},"A","热源温度突然升高",false,{"key":16,"text":17,"correct":18},"B","机组运转初期溶液浓度过稀",true,{"key":20,"text":21,"correct":14},"C","冷却水温度过低","造成冷剂水污染的原因有以下几点:1)溶液循环量过大。2)发生器液位过高。3)加热量过大，发生器中溶液沸腾过于激烈，将溶液带人冷凝器，特别是机组起动初期，溶液质量分数较低，沸腾更剧烈。4)冷却水温度过低或冷却水流量过大。5)冷冻水温度过高,溶液质量分数低，沸腾激烈。6)溶液中有气泡，表明含有易挥发物质，溶液质量不好。冷剂水污染的排除方法是查找出引起冷剂水污染的部位及原因，予以排除，并进行冷剂水的再生。从冷剂泵出口的取样阀取样，测量其相对密度，若相对密度大于1.04时，应进行冷剂水再生的操作。",{"id":6,"name":24,"category":25,"favorite":26},"制冷与空调设备运行操作","特种作业",0]