[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-848967":3},{"question":4,"library":23},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":22},848967,465,1,"单选题","压缩机运转电流过高是由于()。",[11,15,19],{"key":12,"text":13,"correct":14},"A","电源电压太低",true,{"key":16,"text":17,"correct":18},"B","制冷剂太少",false,{"key":20,"text":21,"correct":18},"C","膨胀阀开启度小","压缩机运转电流过大的原因如下:(1)系统中制冷剂过多。(2)室内外散热器过脏。(3)室内或室外风机不转。(4)电源缺相或三相电压不平衡。(5)制冷系统中有空气。(6)压缩机机械故障。(7)电源电压过高或过低。(8)压缩机内部冷冻油过多或过少。(9)压缩机线圈绕组内部故障。(10)压缩机吸、排气效率下降。(11)压缩机电机线圈受潮，匝间短路。(12)四通换向阀机械卡死或内漏。(13)室内或室外风扇电机反转。(14)压缩机功率与制冷系统不匹配。(15)压缩机运行电容器容量过大或过小。(16)室内离心风扇或二道过滤网脏堵。(17)制冷系统脏堵、水堵、油堵、角阀未开全。",{"id":6,"name":24,"category":25,"favorite":26},"制冷与空调设备安装修理","特种作业",0]