[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-848665":3},{"question":4,"library":23},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":22},848665,465,1,"单选题","控制洁净室内正压不高于预订值的措施是()。",[11,15,19],{"key":12,"text":13,"correct":14},"A","采用余压阀",true,{"key":16,"text":17,"correct":18},"B","调小室内风量",false,{"key":20,"text":21,"correct":18},"C","停止风机运行","洁净室外部空气的渗入是污染干扰洁净室洁净度的重要原因之一。因此，在洁净室与外界、不同等级洁净室之间，应保持一定的压差。洁净室与室外的静压差应大于等于10Pa，不同等级洁净室之间、洁净室与非洁净室之间的静压差应大于等于5Pa。维持一定的正压必须有相应的控制措施。通常用余压阀、回风口阻尼层，以及手动或自动回风阀来控制室内正压。",{"id":6,"name":24,"category":25,"favorite":26},"制冷与空调设备安装修理","特种作业",0]